This panel is used for control of liquid level over the deadband of the pneumatic float valve (approximately 1/4" to 1/2"). The control panel pilots a fill or drain valve that operates a pump. A normally open float valve is used. The output control is "on" (indicator red) when the level is low and is "off" when the level is high (indicator green).

Includes inlet filter, regulator and gage assembly.

The output signal can also be used as a remote indicator signal to operate a visual indicator or a sonic alarm. Use as follows:

Low Level Alarm – use a normally open float valve

High Level Alarm – use a normally closed float valve
Unit of Measure

Description 

N/A Includes inlet filter, regulator and gage assembly

Operation

N/A A pneumatic control panel

Box Dimensions

N/A 4 x 4 x 2-5/8 in

Inlet Air Pressure to Regulator

N/A 50 to 125 psig

Normal Pressure Setting

N/A 50 to 100 psig

Pneumatic Indicator

N/A 1 in diameter red/green

Manual Control

N/A OFF/ON Toggle Valve

Air Filtration

N/A Air should be dry and filtered to 5 microns

Output Air Signal

N/A 50-100 psig (same as regulator pressure setting)

Output Signal

N/A 50-100 psig (same as regulator pressure setting)

Control Action

N/A OFF/ON Toggle Valve

Minimum Input Pressure

N/A 50 psig

Maximum Input Pressure

N/A 125 psig

Minimum Operating Pressure

N/A 50 psig

Maximum Operating Pressure

N/A 100 psig

Operation

N/A A pneumatic control panel

Connection A

N/A 5/32" OD Tube Push-Lock

Screened

N/A None